The nVent Liquid-to-Air (LTA) Sidecar Heat Rejection Unit (HRU) is a completely integrated liquid-to-air heat rejection system that enables up to two racks of liquid-cooled IT equipment when a Facility Water System (FWS) is not available.
The LTA Sidecar comes in a 48U rack with footprint of 600mm (24 inches) wide by 1200mm (48 inches) deep.
The LTA Sidecar comes standard with 14 hot-swap fans in N+1 configuration, a reservoir pump unit (RPU) with N+N hot-swap pumps, a hot-swap controller, a hot-swap concurrently maintainable redundant filtration system, 6 x N+N redundant power supplies, integrated leak detection, leak-free hose connections, and an LED Light Path status panel. Active components such as fans, pumps, power supplies, and liquid connections for filling and draining the system are all located on the front side of the Sidecar HRU for easy access.
Support for GB200 NVL36 and GB200 NVL72 rack configurations with a single GB200 NVL36 rack supported by a single Sidecar HRU (1:1) and a single GB200 NVL72 rack supported by two Sidecar HRUs (2:1) in parallel
LTA Sidecar supports GB 200 NVL72 configuration in a 2:1
CONFIGURATIONS WITH THE NVL36 & NVL72
Integrating liquid cooling into existing data centers can be achieved through specific configurations utilizing NVL36 and NVL72 racks. These configurations are designed as reference for the AI Chipsets. Using an LTA sidecar, you deploy AI Chips in existing data centers with minimal infrastructure swap outs.
WHY DEPLOY LIQUID COOLING WITHOUT FACILITY WATER
Deploying liquid cooling without relying on facility water offers significant advantages, such as avoiding the complexities of facility water infrastructure and reducing operational costs. This approach allows data centers to leverage alternative cooling solutions while maintaining high performance and reliability.
LTA sidecar supports GB200 NVL36 in 1:1 configurations
SCALABILITY OF LTA SIDECARS
LTA Sidecars provide a scalable solution for liquid cooling in data centers. Their modular design allows for easy expansion as cooling demands grow, making them a flexible choice for data centers looking to enhance their cooling capabilities without extensive renovations.
Enablement
- Enables liquid–cooled IT equipment in air–cooled environments
- Localized, closed liquid cooling loop without dependency on any facility liquid infrastructure
- Wide environmental support range
- Standard 48U IT rack form–factor
- Performance optimized for low CFM/kW heat rejection performance
- Support for treated water or glycol mixtures up to 30%
- Stainless steel piping
HOT SWAP AND SERVICEABILITY
- Toolless hot–swap, redundant pumps, fans power supplies, temperature & pressure sensors
- Toolless hot–swap system controller
- Hot–swap, redundant filters
- 25–micron or 50–micron filtration options
- Flexible hose connections allowing installation flexibility
- Top & bottom feed liquid connection points to IT equipment
- Cleanable, reusable filters reduce operating costs
- All hot–swap components are serviceable without interrupting cooling
- Pumps, fans, power supplies, and fill & drain liquid connections located on the front of the unit for ease of service and accessibility